WSF2 - Sets for frozen goods

Refrigeration units for frozen goods in split design enable an uncomplicated handling even with large amounts of waste heat. By separating the evaporator and condensing unit, a wide range of installation options can be implemented on the inside and outside walls of a building. 

Key benefits 

  • Reliability through high operational safety
  • Use of components from well-known manufacturers
  • Cost-optimised operations due to easy installation and high energy efficiency
  • Rapid availability due to pre-assembled, coordinated components
Split mounted refrigeration units >2kW

Split units < 2 kW

Frozen Goods
 ModellWSF2 1000WSF2 1400WSF2 1800
Cooling capacity [W]¹

900

1300

1800

Room volume up to [m³]²

10

12

15

Cold room temperature adjustment range [°C]

-25 to -5

-25 to -5

-25 to -5

Allowed ambient temperature [°C] ³

-15 to +43

-15 to +43

-15 to +43

Refrigerant

R449A

R449A

R449A

Sound pressure level day / night [dB(A)] ⁵

35/35

35/35

39/36

Voltage / Phases / Frequency (V/-/Hz)

230/1/ 50

230/1/ 50

400/3/50

Defrosting type

Electrical

Electrical

Electrical

Dimensions condensing unit D/W/H [mm]

654/942/837

575/1174/842

424/1029/840

Dimensions evaporator D/W/H [mm]

515/928/176

515/928/176

430/752/455

Split units > 2 kW

 ModellWSF2 2600WSF2 3900WSF2 4500
Cooling capacity [W]¹

2600

3900

4500

Room volume up to [m³]²

30

50

60

Cold room temperature adjustment range [°C]

-25 to -5

-25 to -5

-25 to -5

Allowed ambient temperature [°C] ³

-15 to +43

-15 to +43

-15 to +43

Refrigerant

R452A

R452A

R452A

Sound pressure level day / night [dB(A)] ⁵

40/37

40/37

41/38

Voltage / Phases / Frequency (V/-/Hz)

400/3/50

400/3/50

400/3/50

Defrosting type

Electrical

Electrical

Electrical

Dimensions condensing unit D/W/H [mm]

840x1030x425

840x1030x425

840x1030x425

Dimensions evaporator D/W/H [mm]

455x752x430

455x1212x430

455x1212x430

¹ Condensing unit; evaporation temperature t₀ -30°C, ambient temperature + 32°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently

² Basis of calculation for room size: room temperature -21°C, ambient temperature +25°C
  Heat extraction from goods 15K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day

³ Max. compressor inlet superheat 20K

⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m