Tecto RF WMF4

In order to provide a complete solution for cold rooms, the wall-mounted refrigeration units are fully integrated into the Viessmann cold room connection concept. The freezer application units are suitable for on-site conditions with little room height and score with their variability: applicable for freezer rooms up to 20m² they can be used for all relevant goods and in all relevant european climate classes. 

Key benefits

  • Sustainable unit with natural refrigerant to reduce the environmental footprint (GWP 3)
  • Increased energy efficiency thanks to minimized need of electrical energy with hot gas defrosting
  • Applicable for a wide temperature range (-25° to -5°C) for safe storage of a variety of goods
  • Fast and easy installation and operation with standardised plugs and controller
  • A durably tight refrigeration cycle guarantees safe and reliable operation


Tecto RF WMC4 WMF4
Specifications
ModellWMF4 600WMF4 850WMF4 ​1200WMF4 ​1800
Cooling Capacity [W] ¹

585/515

845/740

1170/1000

1830/1560

EER ¹

0,94/-

0,83/-

1,02/-

0,91/-

Cold room temperature adjustment range [˚C]

-25 ... -5

-25 ... -5

-25 ... -5

-25 ... -5

Allowed ambient temperature [°C]

+5 ... +43

+5 ... +43

+5 ... +43

+5 ... +43

Refrigerant / GWP²

R290/3

R290/3

R290/3

R290/3

Quantity [kg]

<0,15

<0,15

2x <0,15

2x <0,15

Sound pressure [dB(A)] ³

23

25

26

28

Voltage [V] / Phases / Frequency [Hz]

230/1/50

230/1/50

230/1/50

400/3/50

Defrosting type

Hot gas

Hot gas

Hot gas

Hot gas

Dimensions HxWxD [mm]

728 x 529 x 1075

728 x 529 x 1075

778 x 907 x 1079

778 x 907 x 1079

¹ Standard point A-20/A32 and A-20/A43°C (EN17432)
² Based on AR6 / IPCC
³ A-weighted equivalent sound pressure level at a distance of 10m

Cooling units with winter regulation (WR) down to -10˚C ambient temperature

ModellWMF4 600 WRWMF4 850 WRWMF4 1200 WRWMF4 1800 WR
Cooling Capacity [W] ¹

585/515

845/740

1170/1000

1830/1560

EER ¹

1,18/-

0,87/-

1,15/-

0,84/-

Cold room temperature adjustment range [˚C]

-25 ... -5

-25 ... -5

-25 ... -5

-25 ... -5

Allowed ambient temperature [°C]

-10 ... +43

-10 ... +43

-10 ... +43

-10 ... +43

Refrigerant / GWP²

R290/3

R290/3

R290/3

R290/3

Quantity [kg]

<0,15

<0,15

2x <0,15

2x <0,15

Sound pressure [dB(A)] ³

23

25

26

28

Voltage [V] / Phases / Frequency [Hz]

230/1/50

230/1/50

230/1/50

400/3/50

Defrosting type

Hot gas

Hot gas

Hot gas

Hot gas

Dimensions HxWxD [mm]

728 x 529 x 1075

728 x 529 x 1075

778 x 907 x 1079

778 x 907 x 1079

¹ Standard point A-20/A32 and A-20/A43°C (EN17432)
² Based on AR6 / IPCC
³ A-weighted equivalent sound pressure level at a distance of 10m

Click to read our Tecto Refrigeration Units brochure